Modell ONS-CTV-A

  • AC-Stromsensor für HOBO-Logger
  • 0 … 20 A (600 VAC, 50/60 Hz)
  • Kabellänge 1,8 Meter
  • Direkter Anschluss an Eingangsbuchsen von Loggern der Serien U12 und ZW
  • Für Inneneinsatz
Angebot anfordern

A split-core AC current sensor responsive over the range of 2 to 20 amps AC for use with U12, UX120 and ZW data loggers with external input channels. With an input current of AC current, sine wave, single phase 50 Hz or 60 Hz, load power factor 0.5 to 1.0 lead or lag.

The molded-plastic housing is rated for indoor use per UL508.


Spezifikationen
Technical Specifications
Current Range0-20 AMPS AC
Accuracy with U12±4.5% of full scale (includes logger accuracy)
Accuracy with ZW±4.0% of full scale (includes data node accuracy)
Accuracy with UX120-006M±2.1% of full scale (includes logger accuracy)
Response time (from 10% to 90% of amplitude)Approx. 440 milliseconds
Input CurrentAC current, sine wave, single phase 50 Hz or 60 Hz, load power factor 0.5 to 1.0 lead or lag
Output0-2.5 V DC
Voltage rating600 V AC
Temperature rating-15° to 60°C
Physical Specifications
ConstructionMolded plastic housing for indoor use per UL508
Cable1.8 m
Window Size28 x 20 mm
Dimensions79 x 71 x 36 mm


Broschüre
Betriebsanleitung
PDF Download - 126 KB

Datenlogger > Sensoren für Datenlogger
ModellMess-/Überwachungs­größeMess-/Über­wachungs­bereichKabellänge
ONS-CTV-B
  • Wechselstrom
  • 0 … 50 A (600 V, 50/60 Hz)
  • 1,8 m
ONS-CTV-C
  • Wechselstrom
  • 0 … 100 A (600 V, 50/60 Hz)
  • 1,8 m
ONS-CTV-D
  • Wechselstrom
  • 0 … 200 A (600 V, 50/60 Hz)
  • 1,8 m
ONS-CTV-E
  • Wechselstrom
  • 0 … 600 A (600 V, 50/60 Hz)
  • 1,8 m